{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

When using the LA9F103 finger safe terminal block are lug required in addition to the terminal block?

Issue:
Are lugs required in addition to terminal block when using  LA9F103?

Product Line:
Tesys F Line Contactors and Accessories

Environment:
US Products

Cause:
Product Features

Resolution:
No, the LA9F103 is used in place of lugs by fitting over the three stabs on the F-Line contactor. Acceptable wire sizes are #6 to 300 mcm conductors.

Schneider Electric Canada

Explore more
Category:
Relays – Interface
Explore more
Category:
Relays – Interface
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.