When using the LA9F103 finger safe terminal block are lug required in addition to the terminal block?

Issue:
Are lugs required in addition to terminal block when using  LA9F103?

Product Line:
Tesys F Line Contactors and Accessories

Environment:
US Products

Cause:
Product Features

Resolution:
No, the LA9F103 is used in place of lugs by fitting over the three stabs on the F-Line contactor. Acceptable wire sizes are #6 to 300 mcm conductors.