{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Do the Micrologic trip unit protective relay functions have ANSI certification?
Issue:
Micrologic trip unit protective relay functions characteristics

Product Line:
NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS

Environment:
NEMA SolidState overload relays

Resolution:
No. Our advanced protection functions in the Micrologic P/H trip units are not certified to ANSI C37.2 which requires a 30A output that the M6C cannot deliver.
The basic trip unit functions (overload, short circuit, instantaneous & ground fault) were qualified to ANSI C37.17 and C37.50 as part of the NW qualification.

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: