{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What are the contact ratings on a RPF2B** relay?

Issue:
Contact rating on RPF2B relay

Product Line:
Relays and Timers

Environment:
Zelio RPF Power Relays

Resolution:
The NO contacts are rated 30 amps and the NC are rated only 3 amps. The NC contacts are designed for signaling purposes. If 2 relays are mounted side-by-side there must be a 13mm gap between them to maintain the 30 amps, otherwise that figure drops to 25 amps. All contacts are also 250 vac/vdc rated.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: