Search FAQs
How many 3-pole branch breakers can be installed in an MPZ30T2F?
Issue:
Breakers for MPZ products
Product Line:
LV Transformers
Environment:
Applies to Mini Power Zone Transformers by SquareD/Schneider Electric
Cause:
Mini Power Zone Transformers branch breaker capacity
Resolution:
The MPZ30T2F uses a 30 Circuit interior. 3 spaces are taken up by the backfed main breaker. The deadfront blocks 3 spaces across from the backed main. The interior will accept a maximum of 8 three pole branch feeder breakers, or 12 two pole branch breakers or 24 single pole branch breakers.
Breakers for MPZ products
Product Line:
LV Transformers
Environment:
Applies to Mini Power Zone Transformers by SquareD/Schneider Electric
Cause:
Mini Power Zone Transformers branch breaker capacity
Resolution:
The MPZ30T2F uses a 30 Circuit interior. 3 spaces are taken up by the backfed main breaker. The deadfront blocks 3 spaces across from the backed main. The interior will accept a maximum of 8 three pole branch feeder breakers, or 12 two pole branch breakers or 24 single pole branch breakers.