Are the P1200 circuit breaker enclosures suitable for use as service entrance equipment?

Article available in these languages: Spanish

Issue:
Application

Product Line:
Circuit Breaker Enclosure

Resolution:
Yes, these circuit breaker enclosures are marked: "Suitable for use as service equipment". For use on a 3 phase, 4 wire voltage system, purchase a neutral assembly separately and field install. For service equipment applications, bond the neutral to the enclosure with the neutral bonding strap included with the neutral assembly.