Can two different gauge wires be placed under the same lug of a safety switch that allows for more than one conductor on the lug?
Issue:
Can two different conductor sizes be used on the same lug for safety switches?

Product Line:
Safety Switch

Environment:
Lugs of Safety Switch

Resolution:
No. The lug ratings do not allow for different gauge wires under same lug. All multiple conductors under a lug must be the same size.

Schneider Electric Canada

Can two different gauge wires be placed under the same lug of a safety switch that allows for more than one conductor on the lug?
Issue:
Can two different conductor sizes be used on the same lug for safety switches?  

Product Line:
Safety Switch

Environment:
Lugs of Safety Switch

Resolution:
No. The lug ratings do not allow for different gauge wires under same lug. All multiple conductors under a lug must be the same size.

Schneider Electric Canada

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.