Can single pole (1-Pole) QO Tenant Circuit Breakers be used in the 125A maximum Meter socket positions of the EZM Branch units or MP Metering devices?

Issue:
Product Design

Product Line:
EZM Metering and Meter Pak Metering

Environment:
Tenant breakers

Cause:
Application

Resolution:
Unfortunately No, the tenant breakers for the single phase EZM or MP Metering devices would be considered Service Disconnects and are restricted for use with Two Pole(2-Pole) ONLY, QO Tenant Circuit Breakers.