How many auxiliary contacts can be installed on a LC1D09 to LC1D32 with the Low consumption DC coils?

Issue:
What is the maximum auxiliary contacts that can be added with a D line contactor utilizing a low consumption DC coil?

Product Line:
Tesys D line contactors and accessories

Environment:
Products sold and used in the United States

Cause:
Identifying accessories for D line contactors

Resolution:
Only one two-contact front mounted contact block can be added. No side contacts may be installed. This adds a maximum 2 auxiliary contacts to the front of the device.