What is the difference between instantaneous auxiliary and fault signaling contacts on the GV2?

Issue:
Difference between instantaneous and fault signaling auxiliary contacts

Product Line:
Contactors and Starters - IEC

Environment:
Tesys GV Manual Starter

Resolution:
The instantaneous aux contacts change state to follow the GV2 control as it is mechanically moved to the energized or deenergized position. The fault signaling contacts change state in the event of any fault (i.e. overload or short circuit) condition only. Otherwise, they are not affected by the movement of the control from energized to de-energized state.