Video: Can a Square D by Schneider Electric Sealed Resin Epoxy Encapsulated Transformer with a style A, B, or C enclosure be floor mounted?

Issue:
Would like to mount sealed resin epoxy encapsulated transformer with a style A, B, or C enclosure on the floor.

Product Line:
General Duty Transformers

Environment:
Epoxy Encapsulated Transformers

Cause:
Mounting/Installation

Resolution:
No. Schneider Electric does not offer a floor mounting bracket. The Epoxy Encapsulated transformers require a minimum of 12" clearance from all directions for cooling. This includes the bottom.

NOTE: Epoxy encapsulated transformers are to be mounted on vertical surfaces ONLY.