{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

How many HQO Load centers can I install in an I Line panelboard? Is there a limit ?

Issue:
How many HQO Load centers can I install in an I Line panelboard? Is there a limit ?

Product Line:
I Line panelboard and accessories

Environment:
Application

Cause:
Clarification

Resolution:
There is a maximum of HQO distribution load centers allowed which = 7 . Since there are a max of 6, 1 pole spaces per load center, the maximum amount of QO Branch breakers that could be added would = 42 .  This is due to the solid neutral not being able to support more than that.


Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: