Issue:
The replacement XPSATE relay I have received has one less safety contact (NO) than the XPSAT relay I am replacing.
Product Line:
Preventa Safety Relays - GIC Product
Environment:
Module XPSAT Emergency Stop
Cause:
Product Replacement
Resolution:
The XPSATE safety relays have one less safety output and one more timed contact than the previous XPSAT relays. If the additional safety contact is absolutely needed, then an expansion module (XPSECME or XPSECPE) will be needed as well.
The replacement XPSATE relay I have received has one less safety contact (NO) than the XPSAT relay I am replacing.
Product Line:
Preventa Safety Relays - GIC Product
Environment:
Module XPSAT Emergency Stop
Cause:
Product Replacement
Resolution:
The XPSATE safety relays have one less safety output and one more timed contact than the previous XPSAT relays. If the additional safety contact is absolutely needed, then an expansion module (XPSECME or XPSECPE) will be needed as well.