Replacing XPSAT with XPSATE Safety Relay
Issue:
The replacement XPSATE relay I have received has one less safety contact (NO) than the XPSAT relay I am replacing.

Product Line:
Preventa Safety Relays - GIC Product

Environment:
Module XPSAT Emergency Stop

Cause:
Product Replacement

Resolution:
The XPSATE safety relays have one less safety output and one more timed contact than the previous XPSAT relays. If the additional safety contact is absolutely needed, then an expansion module (XPSECME or XPSECPE) will be needed as well.