LED lights not lighting with LULC08
Issue:
The LULC08 module I have is not lighting the power light when installed.
Product Line:
TeSys U - GIC Product
Environment:
US Product
Cause:
Product Installation
Resolution:
Power must be present on both the communication connection as well as the separate 24Vdc terminals for the unit to function correctly. Please note that this module requires 24Vdc on the communication V+ termination.
The LULC08 module I have is not lighting the power light when installed.
Product Line:
TeSys U - GIC Product
Environment:
US Product
Cause:
Product Installation
Resolution:
Power must be present on both the communication connection as well as the separate 24Vdc terminals for the unit to function correctly. Please note that this module requires 24Vdc on the communication V+ termination.
Released for:Schneider Electric Canada