Issue:
Does it matter whether the 24Vdc power supply for Micrologic Trip Units is grounded or ungrounded?
Product Line:
Micrologic Trip Units
Resolution:
The attached document, 48041-084-01, is included in the carton with the Micrologic trip units. On the second page, it states that the 24 Vdc power must not be grounded.