{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Can the G shunt trip on an F or K frame breaker used with the GFM also be used to trip the breaker from a remote source?
Product Line:
G shunt trip

Environment:
Electrical distribution

Resolution:
No. Applying voltage to the G shunt trip will also apply voltage to the unprotected GFM output and will damage the GFM. Also, the G shunt trip has no coil clearing switch and will burn out on a longer than momentary contact.

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: