Search FAQs
What is the function of the ready-to-close Switch (PF) for the NW or NT breaker?
Issue:
PF switch functionality
Product Line:
Circuit breakers
Resolution:
The ready-to-close position switch (PF) indicates that the following conditions are met and the circuit breaker can be closed:
o The circuit breaker is open.
o The closing springs are charged.
o All interlocks are satisfied.
o There are no standing closing or opening orders.
PF switch functionality
Product Line:
Circuit breakers
Resolution:
The ready-to-close position switch (PF) indicates that the following conditions are met and the circuit breaker can be closed:
o The circuit breaker is open.
o The closing springs are charged.
o All interlocks are satisfied.
o There are no standing closing or opening orders.