Issue:
What are the voltage options / codes for a surge protection device (SPD)
Environment:
Surge Protection
Cause:
Must know the EXACT voltage system that the SPD will be applied to, for example, voltage readings from L-G, L-N, and L-L. If you are not able to provide voltages readings the please specify if the voltage system is a Wye, Delta, High-Leg Delta (HLD), High-Resistance Ground (HRG), Single Phase, or Split-Phase. Please also provide the peak surge current rating that is needed or any other specifications so that we can provide an accurate SPD solution. For example, surge counter, specific enclosure, EMI/RFI filtering, Type 1, Type 2, or integral disconnect switch.
Resolution:
Select the correct voltage code needed for your SPD installation and voltage requirement
SE / ASCO Voltage Code | Voltage Description |
01 / 120S | 120/240V 1Ph 3W + G (Split Ph) |
02 / 120Y (Note 1) | 208Y/120V 3Ph Wye 4W + G |
03 / 240H | 240/120V HLD (Phase B High-Leg) |
04 / 277Y (Note 2) | 480Y/277V 3Ph Wye 4W + G |
05 / 480D (Note 3) | 480V DELTA 3Ph Delta 3W + G |
06 / 240D | 240V DELTA 3Ph Delta 3W + G |
08 / 347Y | 600Y/347V 3Ph Wye 4W + G |
09 / 600D (Note 4) | 600V DELTA 3Ph Delta 3W + G |
12 / 240N (Note 5) | 240V 1Ph 2W + G |
18 / 240S (Note 6) | 480/240V 1P (Split Phase) |
11 / 120N (Note 7) | 120V 1Ph 2W + G (Split Ph) |
1. 208Y/120 series also applies to the following voltage 220Y/127
5. Only available in the EMB series (EMB72F)
6. Only available in the EMB series (EMBA2F)
7. Only available in the EMB series (EMB02F)