Tesys Island : Parameter apply is not allowed in current state of the device (Machine Expert)
Issue:
Changing a parameter or storing a new configuration from machine expert to Tesys Island is not possible due to following message:

Not exclusive control over the island


Product line:
IEC Contactors and Starters

Environment:
Tesys Island Motor management System

Resolution:
Changing settings or storing a new configuration is only allowed by one tool at a time.  Tool includes OMT and DTM.  Check to see if you have the OMT or another DTM connected and close that connection, then retry.