What are the pinouts for the Output Relay on the Environmental Monitoring Unit (AP9319) and the Environmental Management System (AP9320)?


Below are the pinouts:


 

Pin #

 Description

 1

 No Connection

 2, 3

 Normally Closed (NC) Contact

 4, 5

 Common

 6, 7

 Normally Open (NO) Contact (recommended connection)

 8

 No Connection


Relay ratings: 1A, 30V AC/DC



Since the user interface allows for either 'normally open' or 'normally closed,' APC recommends using only the normally open contacts and configuring the 'normal' state in the user interface.



 