Prohledejte časté dotazy
What is the UL listed SCCR rating of a D10 disconnect switches?
Issue:
SCCR for D10 disconnect switch
Product Line:
NEMA Style Door-Mounted Disconnect Switches
Environment:
NEMA Style Disconnect Switches
Resolution:
D10S1 and D10S1H - 5,000 Amperes unless used with Class R or J fuses
For D10S3/D10S3H and D10S4/D10S4H - 10,000 Amperes unless used with Class R or J fuses
NOTE: D10 Disconnect switches have already been discontinued. Contact Technical support for replacement.
SCCR for D10 disconnect switch
Product Line:
NEMA Style Door-Mounted Disconnect Switches
Environment:
NEMA Style Disconnect Switches
Resolution:
D10S1 and D10S1H - 5,000 Amperes unless used with Class R or J fuses
For D10S3/D10S3H and D10S4/D10S4H - 10,000 Amperes unless used with Class R or J fuses
NOTE: D10 Disconnect switches have already been discontinued. Contact Technical support for replacement.
Publikováno pro:Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada: