User name and password lengths for InfraStruXure Central and Netbotz appliances for an SNMP version 3 inform.
Issue:

User name and password lengths for InfraStruXure Central and Netbotz appliances for an SNMP version 3 inform.

Product Line:

NetBotz
InfraStruxure Central

Environment:

Netbotz SNMP v3

Cause:

SNMP version 3 requirements

Resolution:

v3 informs only work under certain circumstances.

md5/des user/password must be 8-15 characters
md5/aes user/password must be 8-15 characters
sh1/aes user/password must be 16+ characters
sh1/des user/password must be 16+ characters

for md5 the user name and password only work if they are between 8-15 characters.
for sh1 the user name and password only work if they are >16 characters.

Schneider Electric Česká republika

User name and password lengths for InfraStruXure Central and Netbotz appliances for an SNMP version 3 inform.
Issue:

User name and password lengths for InfraStruXure Central and Netbotz appliances for an SNMP version 3 inform.

Product Line:

NetBotz
InfraStruxure Central

Environment:

Netbotz SNMP v3

Cause:

SNMP version 3 requirements

Resolution:

v3 informs only work under certain circumstances.

md5/des user/password must be 8-15 characters
md5/aes user/password must be 8-15 characters
sh1/aes user/password must be 16+ characters
sh1/des user/password must be 16+ characters

for md5 the user name and password only work if they are between 8-15 characters.
for sh1 the user name and password only work if they are >16 characters.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.