Article available in these languages: Španělština

Issue:

Why won't my Back-UPS CS run longer than 45mins with a low load connected?

Product Line:

Back-UPS CS

Environment:

BK350, BK500, BK500BLK BK350EI and BK500EI

Cause:

Safety Runtime Limiter

Resolution:

The 120v and 230V International Back-UPS CS models BK350EI and BK500EI, that were made before January 1st 2004, have a max runtime limiting cap of 45 minutes. Anything made after that date will not have a runtime cap. Instead with out the shutdown software they will run until then have exhausted their battery.

Schneider Electric Česká republika

Back-UPS CS: Runtime does not exceed 45 minutes

Article available in these languages: Španělština

Issue:

Why won't my Back-UPS CS run longer than 45mins with a low load connected?

Product Line:

Back-UPS CS

Environment:

BK350, BK500, BK500BLK BK350EI and BK500EI

Cause:

Safety Runtime Limiter

Resolution:

The 120v and 230V International Back-UPS CS models BK350EI and BK500EI, that were made before January 1st 2004, have a max runtime limiting cap of 45 minutes. Anything made after that date will not have a runtime cap. Instead with out the shutdown software they will run until then have exhausted their battery.
 

Schneider Electric Česká republika

move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.