{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
Why does PowerChute Network Shutdown not establish communications with Network Management Card when entering Radius user?
Issue:
PowerChute Network Shutdown will not establish communications with the Network Management Card when Radius is enabled.

Product Line/s:
PowerChute Network Shutdown
Network Management Cards (NMC) AP9630, AP9631, AP9635CH, AP9635, AP9640, AP9641

Environment:
All support OS

Cause:
PowerChute Network Shutdown does not support radius authentication.

Solution:
For AP9630, AP9631, and AP9635 running firmware 6.8 and above and all AP9640 and AP9641, you should enter a PowerChute user that will only be used by PCNS to communicate with the NMC. PCNS and the NMC will not utilize the Radius user. Go to Configuration—Shutdown and add the PowerChute user and authentication phrase.

PowerChute Shutdown Parameters for NMC firmware 6.8 and above

For AP9630, AP9631, and AP9635, running firmware 6.0 to 6.7.x PCNS and the NMC will not utilize the Radius user. Log into the NMC and verify the default apc user is enabled or create a new device or administrator user the PCNS and the NMC will use for communication. Then go to Configuration - Shutdown and select the PowerChute user from the username dropdown menu. The PowerChute username dropdown menu is populated with local users that have Administrative or Device user privileges.
PowerChute Shutdown Parameters for firmware older then 6.7.x

Note: AP9617, AP9618, AP9619 are no longer support.

Schneider Electric Česká republika

Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: