ATV71: Why is the drive tripping on an INF8 code, (internal power supply fault)?
Issue:
INF8 code, (internal power supply fault) on ATV71

Product Line:
Altivar ATV61 and ATV71

Environment:
All types

Cause:
The control supply voltage is to incorrect.

Resolution:
Check the control supply voltages between +24vdc and com or +24V and 0V.
If using an external supply check +24Vdc supply connect between P24 and 0V, and insure the voltage is greater than 19Vdc and does not exceed 30vdc.

Schneider Electric Česká republika

ATV71: Why is the drive tripping on an INF8 code, (internal power supply fault)?
Issue:
INF8 code, (internal power supply fault) on ATV71

Product Line: 
Altivar ATV61 and ATV71

Environment:
All types

Cause:
The control supply voltage is to incorrect.

Resolution:
Check the control supply voltages between +24vdc and com or +24V and 0V. 
If using an external supply check +24Vdc supply connect between P24 and 0V, and insure the voltage is greater than 19Vdc and does not exceed 30vdc.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.