Forced objects reset on a power cycle because the customer has made a Project Backup.
When a Project backup is made, every power cycle will cause a cold restart (%S0). This cold restart
will reset all Forced objects.
For Behavior of Forced Variables Between Modsoft - NxT - Concept and Unity Pro see attached.