ION Setup crashes after splash screen with application error.

Goals and Symptoms

ION Setup Crash Memory Error

ION Setup V2.0 crashes after the splash screen with the following application error:

Error message

The instruction at '0x77e2b31b' referenced memory at '0x00000006'.  The memory could not be 'read'.

Symptoms

When launching ION Setup, the above error displays.

Causes and Fixes


Cause

The file IONSETUP.DAT is corrupt. This problem may occur if the file is 0 bytes in size.


Resolution

Backup IONSETUP.DAT and restart ION Setup. A new file is generated; it is located in the root of the ION Setup installation. The network setup configuration will be lost unless you can recover it from the old file.

Schneider Electric Česká republika

ION Setup crashes after splash screen with application error.

Goals and Symptoms

ION Setup Crash Memory Error

ION Setup V2.0 crashes after the splash screen with the following application error:

 Error message

The instruction at '0x77e2b31b' referenced memory at '0x00000006'.  The memory could not be 'read'.

Symptoms

When launching ION Setup, the above error displays.

Causes and Fixes


Cause

The file IONSETUP.DAT is corrupt. This problem may occur if the file is 0 bytes in size.

 
Resolution

Backup IONSETUP.DAT and restart ION Setup. A new file is generated; it is located in the root of the ION Setup installation. The network setup configuration will be lost unless you can recover it from the old file.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.