{}

Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Jak vám dnes můžeme pomoci?
Ethernet ports and socket summary on ION meters

Article available in these languages: Španělština

Issue 
A user would like to know the total allowable simultaneous connections on ION meters

Product Line
ION Meters ( 9000, 8800, 8650/8600, 7650/7550, 7350/7330/7300, 7700, ACM3720) and PM8000

Environment  
TCP/IP network sockets

Resolution 
The table below summarizes the Ethernet Ports (sockets) available on ION meters
Meter(s)Total Allowable Simultaneous ConnectionsProtocolTCP Port / socketMaximum Connections per Protocol
ION90008 connections total allocated to all protocolsION7700 8
  EtherGate (Com1)7801 1
  EtherGate (Com4)7802 1
  DNP20000 3
  IEC 61850102 5
  Modbus TCP502 8
  Modbus RTU7701 8
  Telnet23 1
  FTP21 2
  Webserver (HTTP)80 10
  Secure webserver (HTTPS)443 10
PM80008 connections total allocated to all protocolsION7700 8
  EtherGate COM17801 1
  DNP 3.020000 3
  IEC 61850102 5
  Modbus TCP502 32
  Modbus RTU7701 4
  Telnet23 1
  FTP21 1
  Web server (HTTP)80 1
ION 86508 connections total allocated to all protocolsION7700 8
  EtherGate COM17801 1
  EtherGate COM47802 1
  DNP 3.020000 3
  IEC 61850102 5
  Modbus TCP502 8
  Modbus RTU7701 8
  Telnet23 1
  FTP21 1
  Web server (HTTP)80 1
ION 8600(V330)
, 8800(V334)
4 connections total allocated to all the protocolsION7700 4
  Modbus RTU7701 4
  Modbus TCP502 4
  EtherGate COM17801 1
  EtherGate COM27802 1
  Telnet23 1
  DNP20000 3
  Modbus Master502 10
ION 7500, 7550*
7600, 7650*
8300, 8400 8500
* Firmware revisions prior to V350
4 connections total allocated to all the protocolsION7700 4
  Modbus RTU7701 4
  Modbus TCP502 4
  EtherGate COM17801 1
  EtherGate COM27802 1
  Telnet23 1
ION 7550*, 7650*
With V350 Firmware
4 pooled socket connections in total allocated to all the protocolsION7700 4
  Modbus RTU7701 4
  EtherGate COM17801 1
  EtherGate COM27802 1
  Telnet23  1
  DNP20000 3
  Modbus TCP*502 32
ION 7700 / Xpress Card1 max connection from either: ION or Modbus RTU.
1 max telnet session, independent of other connections.
ION7700 1
  Modbus RTU7700 1
  EtherGate COM2 and COM3 simultaneously7800 1
  EtherGate COM2 only7802 1
  EtherGate COM3 only7803 1
  Telnet23 1
ION 7300, 7330, 7350-1 max dedicated ethergate connection
-1 max connection from either: Telnet, ION Modbus RTU or Modbus TCP
- The EtherGate and ION/etc connections are independent of each other (i.e. not pooled together)
ION7700 1
  Modbus RTU7701 1
  ModBus TCP502 1
  EtherGate - COM27802 1
  Telnet23 1
ACM 3720 3720 Protocol3721 1 to 3
  Modbus RTU3722 1 to 3
  Telnet23 1

Schneider Electric Česká republika

Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.