Issue:
Disable the keys on the faceplate of the ATV212 and ATV21.
Product line:
Altivar 21/212
Environment:
All models, all serial numbers
Cause:
How to disable the functionality of the buttons on the faceplate of the ATV21/212?
Resolution:
Press mode button to AUF
Press down arrow to F--- Press enter
Press down arrow to F730 (Up/down key reference) set to 1 (disable) press enter
Press down arrow to F732 (Loc/Rem key) set to 1 (disable) press enter
Press down arrow to F733 (Run/Stop key) set to 1 (disable) press enter
Press down arrow to F734 (Priority stop) set to 1 (disable) press enter
Press down arrow to F735 (HMI reset button) set to 1 (disable) press enter
Disable the keys on the faceplate of the ATV212 and ATV21.
Product line:
Altivar 21/212
Environment:
All models, all serial numbers
Cause:
How to disable the functionality of the buttons on the faceplate of the ATV21/212?
Resolution:
Press mode button to AUF
Press down arrow to F--- Press enter
Press down arrow to F730 (Up/down key reference) set to 1 (disable) press enter
Press down arrow to F732 (Loc/Rem key) set to 1 (disable) press enter
Press down arrow to F733 (Run/Stop key) set to 1 (disable) press enter
Press down arrow to F734 (Priority stop) set to 1 (disable) press enter
Press down arrow to F735 (HMI reset button) set to 1 (disable) press enter
Publikováno pro:Schneider Electric Česká republika

