{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
How to reset the password of the FlexNet Publisher back to default

Issue
The FlexNet Publisher (FNP) is a web interface hosted on the PME server for configuring licensing components.

The URL is http://localhost:8090 and the service is called "lmadminSchneider".

The default user name and password for FlexNet Publisher (FNP) is admin/admin.

If the password is changed to something else, the default admin/admin combination will not work.

Product Line
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x
NOTE: Does NOT apply to PME 9.0 and greater

Environment
FlexNet Publisher

Cause
The default password has been changed (admin is the default password).

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location
that will not be overwritten (i.e. the Desktop).


*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

Following the procedure below, the password of the FlexNet Publisher can be reset to its default: "admin" (without the quotation mark).
  1. Navigate to:
    On Power Monitoring Expert 7.2.x:
    C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Floating License Manager\FLEXnet Publisher License Server Manager\conf

    On Power Monitoring Expert 8.x
    C:\ProgramData\Schneider Electric\Floating License Manager\FLEXnet Publisher License Server Manager\conf
  2. Open the 'server.xml' in Notepad or any suitable XML editor.
  3. Search for: lastName="Administrator"
  4. Replace the contents of the password field as shown below:
    id="admin" lastName="Administrator" password="(ENC-01)AxlKxBaCLbp4iPFsjJ6eOFtE+qoJWH8ThHIKN9DgdEgILS9j" passwordExpired="false"

    For example if you want to change the password back to admin, here is what the line would look like:
    id="admin" lastName="Administrator" password="admin" passwordExpired="false"
  5. Restart the "lmadminSchneider" service from 'Services'.
  6. Login to the Flexnet Publisher by navigating to http://localhost:8090  and clicking on 'Administration'. Use the following credentials to sign in if the password was changed to "admin" on step 4:
    Username: admin
    password: admin

    Note: The user name is always "admin"

Schneider Electric Česká republika

Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: