{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.

Prohledejte časté dotazy

Why would the ATV Altivar drive reset back to a factory default when you plug in the CANopen network cable?

Issue:
Altivar drives are resetting back to a factory default when you plug in the CANopen network cable.

Product Line:
Altivar ATV31, ATV312, ATV61, ATV71, ATV32

Environment:
All with CANopen network

Cause:
The drive configuration is reset back to factory default.

Resolution:
1.) Verify that the PLC is not communicating to the command word CMI address 8504.  Setting Bit 0 to 1 will reset the drive back to a factory default.
2.) Verify that the Bootup Procedure Configuration in the PLC does not have "Restore all parameters" selected. Make sure this is NOT selected.

Schneider Electric Česká republika

Přílohy

ATV32_cnM340_01.pdfATV32_cnM340_01.pdf [117.57 KB]
Canopen h507694_0.pdfCanopen h507694_0.pdf [41.98 KB]
Zjistěte více
Řada:
Altivar 32Altivar 71Altivar 61
Zjistěte více
Řada:
Altivar 32Altivar 71Altivar 61