Stabiloy cables with Altistart Soft starts
Issue:
Can you use Stabiloy?
Product Line:
Altistart Soft starts
Environment:
All
Cause:
Stabiloy is an Aluminum/Copper Hybrid
Resolution:
Per the Installation Manual, Only Copper Cables are compatible with Schneider Electric Soft start terminals. Can use Stabiloy only on the high hp range that require lugs. You will, however, have to use Stabiloy compatible lugs to use those cables.
Aug 2014, Per US Engineering.