What is and how to configure JOG in Altivar 71 Drives?

Product Line:
All ATV61/71

Environment:
All environments

Cause:
Fixing a JOG speed or configuring a JOG input.

Resolution:
The jog function allows the user to run at preset speed equal to or less than 10hz when an assigned input is activated.
Jog function assignment can be found in the Application Function Menu.

To configure the JOG :
[1.7 APPLICATION FUNCT.]
[JOG]
"JOG" select the input
"JGF" select JOG speed

Schneider Electric Česká republika

What is and how to configure JOG in Altivar 71 Drives?

Product Line:
All ATV61/71

Environment:
All environments

Cause:
Fixing a JOG speed or configuring a JOG input.

Resolution:
The jog function allows the user to run at preset speed equal to or less than 10hz when an assigned input is activated. 
Jog function assignment can be found in the Application Function Menu. 

To configure the JOG :
[1.7 APPLICATION FUNCT.]
[JOG]
"JOG" select the input
"JGF" select JOG speed

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.