Issue:
Accessing webpage on ATV61 ATV71 VFDs.
Product Line:
Altivar 61 and 71 drives
Environment:
All models and serial numbers with Ethernet IP option card VW3A3316
Cause:
Java 1.8 is not supported or web server services are not activated.
Resolution:
First, verify that web server services are activated via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Web server services are not deactivated.
Accessing webpage on ATV61 ATV71 VFDs.
Product Line:
Altivar 61 and 71 drives
Environment:
All models and serial numbers with Ethernet IP option card VW3A3316
Cause:
Java 1.8 is not supported or web server services are not activated.
Resolution:
First, verify that web server services are activated via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Web server services are not deactivated.
Next, check your computer's Java version, and if 1.8 or later is installed, roll back the Java version to 1.7.67. See the document attached.
Publikováno pro:Schneider Electric Česká republika
Issue:
Accessing webpage on ATV61 ATV71 VFDs.
Product Line:
Altivar 61 and 71 drives
Environment:
All models and serial numbers with Ethernet IP option card VW3A3316
Cause:
Java 1.8 is not supported or web server services are not activated.
Resolution:
First, verify that web server services are activated via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Web server services are not deactivated.
Accessing webpage on ATV61 ATV71 VFDs.
Product Line:
Altivar 61 and 71 drives
Environment:
All models and serial numbers with Ethernet IP option card VW3A3316
Cause:
Java 1.8 is not supported or web server services are not activated.
Resolution:
First, verify that web server services are activated via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Web server services are not deactivated.
Next, check your computer's Java version, and if 1.8 or later is installed, roll back the Java version to 1.7.67. See the document attached.