What are the limitations of the Modbus TCP IO Scanner of a TM251MESE?

The limitation of the Modbus TCP IO Scanner of a TM251MESE are:
- maximum 64 channels divided between maximum 64 slaves.
Each channel has the following limitations:
- for Read/Write Holding Registers the maximum length is 125 read words  and 121 write words
- for Read Holding Registers the maximum length is 125 words
- for Write Multiple Registers the maximum length is 123 words

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

What are the limitations of the Modbus TCP IO Scanner of a TM251MESE?

The limitation of the Modbus TCP IO Scanner of a TM251MESE are:
- maximum 64 channels divided between maximum 64 slaves.
Each channel has the following limitations:
- for Read/Write Holding Registers the maximum length is 125 read words  and 121 write words
- for Read Holding Registers the maximum length is 125 words
- for Write Multiple Registers the maximum length is 123 words

 

If this FAQ did not solve your issue, you can chat with us at  chat with us  or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.