{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
Why does the local/remote button not work on the ATV212 drive?

Issue:
ATV212 local/remote button is not working.

Product Line:
Altivar 212, ATV212

Environment:
All

Cause:
N/A

Resolution:
The button might have been disabled. To check this:

  1. From 0.0, press mode and arrow down to F---.
  2. Press enter and arrow up to F732.
  3. Press enter and make sure it is set to 0 (enabled).

image1

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: