Issue:
ATV312 how to set up a permissive run
Product Line:
Altivar 312, ATV312
Environment:
All
Cause:
Safety, permissive function.
Resolution:
In the programming, go into menus FUn-, StC-, and parameter nSt. Assign nSt to a logic input LIx to act as a permissive.
If that corresponding logic input does not have a +24VDC applied, the drive will show nSt on the display to indicate freewheel stop status.
The freewheel stop / run permissive function applies for both Local and Remote modes of operation.
ATV312 how to set up a permissive run
Product Line:
Altivar 312, ATV312
Environment:
All
Cause:
Safety, permissive function.
Resolution:
In the programming, go into menus FUn-, StC-, and parameter nSt. Assign nSt to a logic input LIx to act as a permissive.
If that corresponding logic input does not have a +24VDC applied, the drive will show nSt on the display to indicate freewheel stop status.
The freewheel stop / run permissive function applies for both Local and Remote modes of operation.