Why does Control Expert (formerly Unity Pro) appear to freeze or lock up when I click on the Data Selection ellipsis ?
The most likely cause for this condition is having recently used an external monitor with your PC.
If you use an external monitor with Unity and disconnect the monitor while the application is still open, the software will appear
to fail when you launch the Data selection screen in your next Unity session. Unity is still directing its GUI to the extended
monitor and will continue to do so until its brought back to the native PC

After you get to the 'frozen' condition, Select  ALT & SPACE then M. This will allow you to use the arrow keys move the window into view.

Schneider Electric Česká republika

Why does Control Expert (formerly Unity Pro) appear to freeze or lock up when I click on the Data Selection ellipsis ?
The most likely cause for this condition is having recently used an external monitor with your PC.
If you use an external monitor with Unity and disconnect the monitor while the application is still open, the software will appear
to fail when you launch the Data selection screen in your next Unity session. Unity is still directing its GUI to the extended
monitor and will continue to do so until its brought back to the native PC  

 After you get to the 'frozen' condition, Select  ALT & SPACE then M. This will allow you to use the arrow keys move the window into view.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.