Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Jak vám dnes můžeme pomoci?
How to display only active alarms in Vista or Diagrams for export
Issue
User wants a list of all current active alarms that can be exported to excel

Product
StruxureWare Power Monitoring (SPM) 7.0.x
Power Monitoring Expert (PME) 7.2.x, 8.x

Environment
Vista and Web Diagrams

Resolution

1) Open Vista and select a current diagram or create a new diagram

2) With the diagram toolbox open, drag and drop a new datalog viewer object

3) Setup the datalog viewer and edit the query and copy and paste the following query.

SELECT [SourceName]
,[SourceType]
,dbo.DateAsUnix(TimestampUTC)  AS timestamp
,[Priority]
,[Cause]
,[CauseValue]
,[Effect]
,[EffectValue]
,[AckTimeUTC]
,[AckUserName]
,[AckRemark]
FROM [ION_Data].[dbo].[vAlarmLog]
where endID is null and (not type = 0) and priority > 64
order by timestamputc desc

4) Save the diagram and open datalog viewer in Vista or web diagram

5) Copy the contents of the table to excel

Schneider Electric Česká republika

How to display only active alarms in Vista or Diagrams for export
Issue
User wants a list of all current active alarms that can be exported to excel

Product
StruxureWare Power Monitoring (SPM) 7.0.x
Power Monitoring Expert (PME) 7.2.x, 8.x

Environment
Vista and Web Diagrams

Resolution

1) Open Vista and select a current diagram or create a new diagram

2) With the diagram toolbox open, drag and drop a new datalog viewer object

3) Setup the datalog viewer and edit the query and copy and paste the following query. 

SELECT [SourceName]
      ,[SourceType]
      ,dbo.DateAsUnix(TimestampUTC)  AS timestamp
      ,[Priority]
      ,[Cause]
      ,[CauseValue]
      ,[Effect]
      ,[EffectValue]
      ,[AckTimeUTC]
      ,[AckUserName]
      ,[AckRemark]
  FROM [ION_Data].[dbo].[vAlarmLog]
  where endID is null and (not type = 0) and priority > 64
  order by timestamputc desc 

4) Save the diagram and open datalog viewer in Vista or web diagram

5) Copy the contents of the table to excel

 

Schneider Electric Česká republika

move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.