{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.

Prohledejte časté dotazy

Inverting CT polarity on EM4000 / EM4800 / E4800 using EM4800 Configuration Tool

Issue
The EM4000 / EM4800 / E4800 is reading incorrectly due to an inverted CT. The customer is not able to physically invert the CT; however he/she would like the meter to read correctly.

Environment
EM4800 Configuration Tool

Resolution
To invert the CT polarity via the EM4800 Configuration Tool, place a negative sign in front of the CT primary value. An example is shown below:

If the CT ratio is 600:5, the Current value should be changed from 600 to -600.
Figure1 Figure 2

The EM4800 Configuration Tool if available for download here: https://www.se.com/us/en/download/document/SEMetershop_V1.6.1.1154/

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada: