Issue:
Altivar Process Drive connection to Ethernet IP network
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Note: This FAQ goes over some basic checks and troubleshooting tips. For extended troubleshooting please refer to your drives Ethernet IP manual.
Drive Will Not Connect
Drive Connects But Will Not Run
Altivar Process Drive connection to Ethernet IP network
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Note: This FAQ goes over some basic checks and troubleshooting tips. For extended troubleshooting please refer to your drives Ethernet IP manual.
Drive Will Not Connect
- Card
- Confirm Card Module is installed. The ATV600 drive (only) has integrated Modbus TCP and not Ethernet IP. Option module card must be used.
- Only works with Firmware V1.5IExx or above for ATV600 drives only. Should work on any ATV900 drive.
- Installation
- Make sure proper Ethernet cable is connected to the appropriate Ethernet serial port.
- Pin Layout - Make sure to use proper pinouts for cables.
- FA314982:https://www.se.com/ww/en/faqs/FA314982/
- Isolate any electrical interference
- Use conduits or other isolating materials
- Separate control and power connections
- Add terminating resistors if the drive is at the end or the last of device in the network.
- Network
- Check for any duplicate addresses on the network.
- Check to make sure you have proper configured assemblies
- Programming
- Check Basic Settings on the drive. Make sure the following is set:
- IP Assignment Mode
- Set to Fixed
- IP Address
- Subnet Mask
- Gateway Address
- IP Assignment Mode
- Check Basic Settings on the drive. Make sure the following is set:
Drive Connects But Will Not Run
- Network
- Verify you can read from the drive
- Verify reading and writing to correct Modbus registers
- Programming on the Drive
- Confirm drive is setup for Network Control
- Check Command and Reference Menu
- [Complete settings] [Command and Reference]
- Important Note!: For ATV600 drives only, the Ethernet IP option is a Communication Module it is not Embedded. When selecting option for Ethernet IP use the option for "Reference Frequency Via Fieldbus Module" [Com. Module] not [Embedded Ethernet]
- [Complete settings] [Command and Reference]
- Check Command and Reference Menu
- Confirm drive is setup for Network Control
- Troubleshooting
- Check Communication Map
- [Display] [Communication map]
- Check Command Channel
- Command Register
- Ref Freq Channel
- Ref Freq
- [Display] [Communication map]
- Disable FDR settings if not using a Faulty Device Replacement.
- Check LEDs on the drive
- The following FAQ describes the LEDs status for Ethernet IP Field-bus for the Altivar Process Drives
- Check Communication Map
- Reference attached manuals for further troubleshooting
Publikováno pro:Schneider Electric Česká republika



