{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
Video: How can a factory reset be performed on an ATV320?

Article available in these languages: Česká, Finština, japonština, Nizozemština

Issue:
Perform a factory reset on an ATV320 drive.

Product Line:
Altivar 320, ATV320

Environment:
All

Resolution:
To perform a factory reset from power up;
Enter on dial.
Scroll down to CONF menu and enter.
Scroll down to FCS- and enter.
Scroll down to FRY- and select all if you would like to reset all parameters (including function blocks). The two vertical lines to the right of 'all' should move up.
ESC back to FRY-.
Scroll down to GFS and enter.
Scroll down to yes and enter (hold for 3 seconds).
The parameter GFS should go to NO automatically.  This is when you know factory reset has been done.

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Schneider Electric Česká republika

Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: