{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.

Prohledejte časté dotazy

Video: How to configure the "DIAGNOSE Mode" of “RENF22R2MMW NFC Timing Relay” product using smart phone?

Article available in these languages: Francouzština, Nizozemština

Step 1 : Product Identification
Step 1.1 Initiate the NFC App
Step 1.2 Select the Read button
Step 1.3 Place the phone in front of NFC Timing Relay.
And adjust the phone until the “Pairing Indication LED” lit-up.
Step 1.4 Below screen appeared when Uploading is successfully executed.

Step 2 : Function & Timing selection
Step 2.1 Select the Function C. Off-delay relay with control signal
Step 2.2 Press the T button and set T = 35s

Step 3 : Loading the DIAGNOSE Mode
Step 3.1 Select <Diagnose> button.
Step 3.2 Press the Read button. Place the phone in front of NFC Timing Relay.
Step 3.3 Below message appeared after Uploading is successfully executed.
Step 3.4 4 - Power Supply Indication (green) LED
Fast Blinking….
to indicate that the product is on <DIAGNOSE> Mode.


Schneider Electric Česká republika

Přílohy

DIAGNOSE Mode_Presentation.pdfDIAGNOSE Mode_Presentation.pdf [1.18 MB]
Zjistěte více
Řada:
Zjistěte více
Řada: