Is the triangle symbol (IEC 60417-5638) mandatory on E-Stop labels?
The article 4.3.7 answers to this question:
4.3.7 Neither the actuator nor the background should be labelled with text or symbols. Where a symbol
is needed for clarification, the symbol from IEC 60417-5638 shall be used, see Figure 2.

Which reference of label is without any marking?
- The ZBY9101 without any marking is still sold
- The ZBY9101M is the ZBY9101 with adapted dimensions to the ZBY160* guards. it cannot replace the ZBY9101
- The 3D label without marking is not created

Schneider Electric Česká republika

Is the triangle symbol (IEC 60417-5638) mandatory on E-Stop labels?
The article 4.3.7 answers to this question:
4.3.7 Neither the actuator nor the background should be labelled with text or symbols. Where a symbol
is needed for clarification, the symbol from IEC 60417-5638 shall be used, see Figure 2.

Which reference of label is without any marking?
- The ZBY9101 without any marking is still sold
- The ZBY9101M is the ZBY9101 with adapted dimensions to the ZBY160* guards. it cannot replace the ZBY9101 
- The 3D label without marking is not created
 

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.