{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
Can an ATV680 Active Front End drive run with unbalanced input voltage?

Article available in these languages: Španělština

Issue:
ATV680 running with unbalanced input voltage

Product Line:
Altivar 680 Process Drives

Environment:
All

Cause:
Site line voltage is unbalanced

Resolution:
It is NOT recommended to operate an ATV680 AFE on a 480V power system with a voltage unbalance of 4% to 7.5%. This is far outside the specification of the drive.
The mains voltage must comply with the requirements according to IEC 60038 and EN 50160:
- Unbalance between phases: < 2 %
- Total harmonic factor THD(v): < 10 %
- Maximum single harmonic: < 5 %
With this supply voltage the drive complies with the specified THDi value.

If the voltage unbalance is 2 … 4% the drive will work but the THDi value will be higher than specified. A voltage unbalance of more than 4% will harm the drive. The input IGBT might overheat and/or the fuses might blow due to unsymmetrical input current. There is also a risk of oscillations if the voltage controller is not able to keep DC bus voltage constant.

Schneider Electric Česká republika

Zjistěte více
Řada:
Kategorie:
Užitečné články
Zjistěte více
Řada:
Kategorie: