{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
How to setup an Alarm Variable in EcoStruxure Operator Terminal Expert (formerly known as Vijeo XD)?
Issue:
Cannot find where in EcoStruxure Operator Terminal Expert (formerly known as Vijeo XD) to create an Alarm Variable.

Product Line:
EcoStruxure Operator Terminal Expert, Vijeo XD 3.0 or higher.

Resolution:




In order to setup an Alarm Variable in Vijeo XD, there are a few steps you need to make.

1) First create an Alarm Group by first selecting "Alarms / Events" and then press the + Alarm Group button

2) Create a variable to use as the Alarm Variable
3) Expand the Alarm Group and choose the type of alarm you would like to create (BOOL / LEVEL)
4) Press the +Alarm Button to add the variable that you created. (See below)

Schneider Electric Česká republika

Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: