On AOA app, why my subscene or picture is displayed as a blue square ?
When I track my scene or open my subscene on AOA app on Apple tablet (Ipad), the picture/subscene is displayed as a blue square.

APA app example:



A Image resolution limitation is present on Apple tablet (4096p x 4096p).
If you build a AOA project with a picture with more than 4096 pixels resolution size, it will be badly managed on apple tablet and will be displayed as a blue square.

Example of image in paint:



User guide:

This limitation is displayed in user guide (limitation ressources section).


Keywords
Ecostruxure augmented operator advisor, IOS tablet, Apple, AOA, blue square, subscene, AOA app

Case author:
Lilian Cabos

Product Familly
Ecostruxure Augmented Operator Advisor