What can cause a CFF fault on the ATV630 and ATV930 Process drives?
Issue:
CFF fault causes on the ATV630 and ATV930 Process drives.

Product Line:
ATV630 and ATV930 Process drives

Environment:
All

Cause:
Option card removed, power board changed and not rated.
Use SoMove service section to identify the cause of the CFF.

Resolution:
At power on the hardware configuration is approved, if option card,
bower board has changed this error occurs.
Probable cause:
Option card removed, power board changed and not rated.
Use SoMove service section to identify the cause of the CFF.

Remedies:
- check all option cards if they are connected correctly.
- check if the power board / control block fit's to the drive.
- If the option card was removed intended, a factory setting needs to be performed

Schneider Electric Česká republika

What can cause a CFF fault on the ATV630 and ATV930 Process drives?
Issue:
CFF fault causes on the ATV630 and ATV930 Process drives.

Product Line:
ATV630 and ATV930 Process drives

Environment:
All 

Cause:
Option card removed, power board changed and not rated.
Use SoMove service section to identify the cause of the CFF.

Resolution:
At power on the hardware configuration is approved, if option card,
bower board has changed this error occurs.
Probable cause:
Option card removed, power board changed and not rated.
Use SoMove service section to identify the cause of the CFF.

Remedies:
- check all option cards if they are connected correctly.
- check if the power board / control block fit's to the drive.
- If the option card was removed intended, a factory setting needs to be performed

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.