{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
Easy-UPS reports bDC <Battery Disconnected>
Issue: Easy-UPS reports bDC <Battery Disconnected> during online operation with battery properly connected

Product lines: SRV1KI, SRT2KI, SRV3KI, SRV1KRI, SRV2KRI, SRV3KRI, SRC1KI, SRC1I-AR, SRC2KI, SRC2KI-AR, SRC1KUXI-IN, SRC1KUXI, SRC1KUKXIX84

Cause: The UPS performs an internal battery self-check every 5 minutes. If the UPS detects the battery voltage has deviated outside the acceptable threshold, the UPS will report bDC <Battery Disconnected>. The alert will auto resolve within 5 minutes at the next battery self-check.

Resolution: Use the attached firmware upgrade guide and the appropriate firmware file to update the UPS firmware and resolve the bDC event.

Schneider Electric Česká republika

Přílohy
Update firmware and software Easy-UPS 1-3kVA.7z [179.19 KB]
Easy-UPS SRV firmware upgrade.pdf [296.17 KB]
Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: