Issue:
How to get the "fastest" possible stop with an ATV320?
Product Line:
ATV320
Environment:
All serial numbers
Cause:
Need a fastest stop time.
Resolution:
With a "beefy" brake resistor that can handle the load.
Go to Full, then Fun menu:
Ramp: brA ( Dec ramp adapt). set to "no"
Then go to Stt [Type of stop]- Set to Fast stop
And Ramp divider ( dcF)- set to 0.