How does an Altivar Drive detect an Input Phase Loss (PHF)?
Issue:
Altivar Process Drives input phase loss detection

Product Line:
Altivar Process Drive

Resolution:
The ATV6x0 and ATV9x0 drives monitor voltage on the input terminals and they can be displayed on the keypad or in SoMove.
However the Phase loss detection does not use those measured values.  Instead the drive monitors the noise (ripple) on the DC bus and will trip if the distortion exceeds a preset level.
The actual level will change based on the voltage range of the drive.
When a motor is lightly loaded the ripple may be within acceptable levels, but as the load increases the drive may trip.
PHF can still be disabled by changing the PHL setting, but this should only be done for testing, or in specific applications when approved by Schneider Electric.

Schneider Electric Česká republika

How does an Altivar Drive detect an Input Phase Loss (PHF)?
Issue:
Altivar Process Drives input phase loss detection

Product Line:
Altivar Process Drive

Resolution:
The ATV6x0 and ATV9x0 drives monitor voltage on the input terminals and they can be displayed on the keypad or in SoMove.
However the Phase loss detection does not use those measured values.  Instead the drive monitors the noise (ripple) on the DC bus and will trip if the distortion exceeds a preset level.
The actual level will change based on the voltage range of the drive.
When a motor is lightly loaded the ripple may be within acceptable levels, but as the load increases the drive may trip.  
 PHF can still be disabled by changing the PHL setting, but this should only be done for testing, or in specific applications when approved by Schneider Electric.
 

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.